Ryan Herco Products Corporation
RHP Header

RELATED INFORMATION:

TECHNICAL NOTES

MAXIMUM OPERATING PRESSURES FOR PIPE & FITTINGS
AT 75°F
IMPORTANT NOTES:
  • All values are based on water service. For more severe service conditions, an additional correction factor may be required.
  • Plastic pipe and fittings are not recommended for air or compressed gas service.
 

MAXIMUM OPERATING PRESSURE (PSI) AT 75°F

NOMINAL
PIPE SIZE

SCHEDULE 40
PVC & CPVC

SCHEDULE 80
PVC & CPVC

SCHEDULE 80
POLYPROPYLENE

SCHEDULE 80
PVDF

Socket
End

Socket
End

Threaded
End

Thermo-Seal
Joint**

Thermo-Seal Joint

Threaded
End

1/2"

600
850
420
410
580
290

3/4"

480
690
340
330
470
235

1"

450
630
320
310
430
215

1-1/4"

370
520
260

1-1/2"

330
471
240
230
320
160

2"

280
400
200
200
275
135

2-1/2"

300
425
210**
185

3"

260
375
190**
185

4"

220
324
160**
160

6"

180
280
N.R.
N.R.

8"

160
250
N.R.

10"

140
230
N.R.

12"

130
230
N.R.
 

* Threaded Polypropylene is not recommended for pressure service.
** For threaded and backwelded joints.
N.R. Not Recommended.
Plastic pipe and fittings are not recommended for air or compressed gas service.

 

1-800-848-1141